New Hammond Power Solutions Centurion D1 dV/dT Filter

April 25, 2022

New Hammond Power Solutions Centurion D1 dV/dT Filter

Hammond Power Solutions (HPS) has a new addition to their line of power quality products – HPS Centurion D1 dV/dT Filter. The HPS Centurion D1 is designed for use between variable frequency drives (VFD’s) and motors when long lead lengths are used. It combines an inductor and parallel resistor network to mitigate both high frequency components and voltage spikes between the VFD and motor.

These filters provide protection for both the motor and cables that power it, and are typically used when the cable length exceeds a value that can lead to high voltage levels caused by reflected wave phenomena. dV/dT filters provide protection to the motor by slowing down the rate of voltage increase and minimizes the damaging peak voltages that occur within the motor’s windings and terminals.

The Hammond Power Solutions Centurion™ D1 dV/dT filter combines an inductor and parallel resistor network to mitigate both high frequency components and voltage spikes between the VFD and motor. The D1 can mitigate the effects of reflected wave voltages greater than what a reactor alone can accomplish. The D1 filter provides protection to the motor by slowing down the rate of voltage increase and minimizes the damaging peak voltages that occur within the motor’s windings and along the length of cables feeding the motor.

DCS New HPS Centurion D1 dVdT Filter 2 400

Operation Principle

The term “dV/dT” refers to the change in voltage over change in time. With regards to VFD’s, dV/dT is explained as the rapid change in voltage at the beginning or end of the square wave pulses that make up the pulse width modulated (PWM) output of a VFD that powers the motor. As the square wave pulses travel the electrical cable to the motor, the differences in impedance between the cable and motor windings cause some energy in the pulse to be “reflected”. In applications where the distance between the motor and VFD is long, the voltage of two pulses can combine in the cable or motor windings. This creates a high voltage condition of twice or more the VFD’s DC bus voltage. Long lead length motor applications can experience peak voltages up to 1600V in a 480V system and up to 2100V in a 600V system. These high peak voltages will cause motor winding failures and premature motor insulation failure resulting in down time and lost revenue.

Typical examples of Hammond Power Solutions Centurion D1 dV/dT filter applications include oil and gas pumps, wastewater treatment plants, HVAC systems, pulp and paper, and irrigation fields.

3 Year Warranty

Features

  • System Voltage Rating up to 600V (480V-600V applications)
  • Current Rating of 2A to 108A (consult HPS for higher ratings)
  • Inverter Switching Frequency 2kHz to 4kHz
  • Inverter Operating Frequency up to 60Hz
  • Insulation System of 130°C (2A – 54A), 180°C (>55A)
  • Voltage Drop of less than 3%
  • Up to 1000ft (600ft & 1000ft models available)1,2
  • Peak Voltage at Motor of 150% of DC bus voltage
  • cUL Listed

Environmental Product Characteristics

  • Ambient Operating Temperature:
    • Open Style: up to 50°C
    • Enclosed Style: up to 40°C
  • Altitude: <1000m
  • Cooling Method: Natural Convection
  • Enclosure Type: Open, Type 1
Notes:

1VFD rated cable recommended
2Maximum motor cable size to achieve 5% voltage drop (including 2% from the filter)
Maximum lead length and carrier frequency can vary depending on motor cable type

Source

Related Product

Hammond Power Solutions: Drive Isolation Transformers – NRCan 2019 Efficiency

The new Hammond Power Solutions Tribune E energy efficient drive isolation transformer is compliant to the latest NRCan efficiency standards.  It is designed based on extensive customer feedback using industry leading technologies and materials to meet the rugged demands of both AC and DC variable speed drives while proving the required voltage change. The windings are designed to withstand overcurrent of 150% of the rated load for 60 seconds or 200% of the rated load for 30 seconds. Drive Isolation Transformers are sized to match standard motor horsepower and voltage ratings.  Standard sizes range from 5 to 600 HP in 7 standard voltages.  Non-standard sizes and voltages are available upon request.

Related Articles



Editor’s Pick: Featured Article

Weidmüller’s u-control 2000: The Automation Controller

Weidmüller’s u-control 2000: The Automation Controller

Weidmüller’s scalable engineering software, u-control 2000, adapts individually to your requirements. And, the u-control is powerful, compact and fully compatible with Weidmüller’s I/O system u-remote. This article looks at what makes u-control the heart of your automation.

Programmable logic controllers (PLCs) are one of the main components of any automated system. A typical control system has inputs, outputs, controllers (i.e., PLCs), and some type of human interaction with the system, a human machine interface (HMI), for example.

Read More



Latest Articles

  • Understanding Industrial Relay Contact Configurations: NO, NC, SPDT, and DPDT

    November 19, 2024 Relays serve as the backbone of industrial control systems, enabling the control of high-power circuits using low-power signals. Understanding different relay contact configurations is crucial for designing effective control systems. Let’s explore the various types of relay contacts and their applications in industrial automation. Basic Contact Types and Their Applications The foundation of… Read More…

  • Training Courses on Plant and Machinery Safety from Pilz

    November 19, 2024 Plant safety is vitally important for the safe operation of technical plants. As a machine manufacturer or operator you are legally obliged to ensure the safety of plant, machinery and devices. Training courses teaches you to identify risks and avoid accidents. Further training for safety officers and employees is the key to success here. With this knowledge… Read More…