Choosing the Right Fuses: Transformers 101

April 23, 2024

Transformers 101: Choosing the Right Fuses

Types of Fuses

Fuses come with a variety of options, each type designed for a specific application. While these fuses may share the same current rating, they have different clearing curves which means some can handle large inrush currents for up to 10 seconds, while some blow right away.

Selection Criteria

When Selecting a fuse, you must consider the following:
  1. Current (Amps)
  2. Voltage
  3. Available Fault Current (Generally measured in kA)
  4. Application (What are you protecting?)

Choosing the Right Size for a Transformer

Determine where you will fuse primary only or primary and secondary and calculate the primary current (Amps).

Use the table below to guide you further:

Primary Fuse

Primary AmpsMax Primary Fuse % Rating
9 or more125*
2 to less than 9167
less than 2300

Primary & Secondary Fuse

Secondary AmpsMax Primary Fuse % Rating
PrimarySecondary
9 or more250125*
less than 9250167
*If 125% does not correspond to a standard ampere rating, the next higher standard rating shall be permitted.

Placement of Fuses

  • Primary Fuse (Input)
    • essential to protect against short circuit and overloads.
  • Secondary Fuse (Output–optional)
    • safeguards against overloading the transformer.

Consider the Starting Current

Primary fuses must be able to handle the high inrush current of a transformer. This can be as much as 30 x calculated current for .01 seconds. A time delay dual-element fuse is recommended.

Check this fuse selection table for control and 3-phase transformer:

vancoelectrical.com/fuse-table

Example

Let’s suppose we have a transformer with the following specifications:

  • Transformer Rating: 45 kVA
  • Primary Voltage: 600V (3-phase)
  • Secondary Voltage: 208/120V (3-phase)

Calculate Primary Current:

Primary Current (A) = kVA x 1000 / √3 x Primary Voltage (V)

Primary Current (A) = 45 kVA x 1000 / √3 x 600 (V)

Primary Current (A) ≈ 45000 /  √3 x 600 (V) ≈ 45000/1039.2 ≈ 43.35 A

Choose Fuse Rating (125% of the calculated primary current)

Fuse Rating (A) = 1.25 x Primary Current (A)

Fuse Rating (A) = 1.25 x 43.35 A

Fuse Rating (A) ≈ 1.25 x 43.35 A ≈ 54.19 A

So, we’d select a fuse close to a rating of 54.19 A, which is 60 A.

Source

More Information

Vanco Electrical Supply Ltd.

Related Story

Discover MTE Through Vanco’s Unmatched Expertise and Service

At Vanco Electrical Supplies, their commitment is not just about providing electrical products; it’s about cultivating partnerships and seizing opportunities to better serve their clients. Founded by Walter Wiebe and Dave Nicoll, their roots in Markham, Ontario were sown with a commitment to offer technically competent representation to emerging manufacturers overlooked by the market.

Related Articles



Editor’s Pick: Featured Article

Weidmüller’s u-control 2000: The Automation Controller

Weidmüller’s u-control 2000: The Automation Controller

Weidmüller’s scalable engineering software, u-control 2000, adapts individually to your requirements. And, the u-control is powerful, compact and fully compatible with Weidmüller’s I/O system u-remote. This article looks at what makes u-control the heart of your automation.

Programmable logic controllers (PLCs) are one of the main components of any automated system. A typical control system has inputs, outputs, controllers (i.e., PLCs), and some type of human interaction with the system, a human machine interface (HMI), for example.

Read More



Latest Articles

  • Vention Introduces AI, Making Adoption of Automation Easier

    December 20, 2024 By Krystie Johnston Vention has been on a mission to democratize automation since 2016. Etienne Lacroix, Founder and CEO of Vention, realized he could leverage software and technology to productize automation, making it more accessible to everyone. While working as an engineer and integrating systems for manufacturers, he noticed added costs and… Read More…

  • Machine Man Reflects on 50 Years In a Challenging But Rewarding Field

    December 18, 2024 Pat McCluskey’s machine design and build experience at ANCA has fuelled manufacturing exports for Australia for half a century For a half-century, ANCA has made the machines that make the tools that make the world go around. One half of its founding pair, Pat McCluskey, has designed many grinding machine tools in… Read More…